3 phases Dry Type Transformer
Insulation Class : 220oC Temperature Rise : 130 & 150oC Taps : 2-2 1/2% FCAN, 2-2 1/2% FCBN. Primary : 480 volts. Secondary : 120/208 volts.
Characteristics
- Copper and Aluminum winding.
- Epoxy impregnation.
- Adjustment Taps at 2-3% FCAN & 2-3% FCBN.
- Nema 2 enclosures up to 100Kva (the standard is Nema1 for bigger units).
Options
- 115oC & 80oC temperature rise.
- Electrostatic shield(s).
- K factor.
- Enclosure types : Nema 3R, Nema 4 ou Nema 12.
- Epoxy impregnated (VPI).
Full Load Current Connectors Type Technical Drawing

| CSA CERTIFICATION | UL CERTIFICATION | |
Full Load Current Full Load Current (amps)
| KVA |
208 |
240 |
347 |
380 |
480 |
600 |
| 6 |
16.7 |
14.4 |
10 |
9.1 |
7.2 |
5.8 |
| 10 |
27.8 |
24.1 |
16.6 |
15.2 |
12 |
9.6 |
| 15 |
41.6 |
36.1 |
25 |
22.8 |
18 |
14.4 |
| 22 |
61.1 |
52.9 |
36.6 |
33.4 |
26.5 |
21.2 |
| 30 |
83.3 |
72.2 |
49.9 |
45.6 |
36.1 |
28.9 |
| 45 |
124.9 |
108.3 |
74.9 |
68.4 |
54.1 |
43.3 |
| 50 |
138.8 |
120.3 |
83.2 |
76 |
60.1 |
48.1 |
| 75 |
208.2 |
180.4 |
124.8 |
114 |
90.2 |
72.2 |
| 112.5 |
312.3 |
270.6 |
187.2 |
170.9 |
135.3 |
108.3 |
| 150 |
416.4 |
360.9 |
249.6 |
227.9 |
180.4 |
144.3 |
| 225 |
624.6 |
541.3 |
374.4 |
341.9 |
270.6 |
216.5 |
| 300 |
832.7 |
721.7 |
422.2 |
455.8 |
360.9 |
288.7 |
Connectors Type Connectors By Phase
| KVA |
Nb |
120- 208 VOLTS |
Nb |
600 VOLTS |
GROUND |
| 6 |
1 |
2-14 |
1 |
2-14 |
2-14 |
| 10 |
1 |
2-14 |
1 |
2-14 |
2-14 |
| 15 |
1 |
2-14 |
1 |
2-14 |
2-14 |
| 22 |
1 |
2-14 |
1 |
2-14 |
2-14 |
| 30 |
1 |
2 / 0-6 |
1 |
2-14 |
2-14 |
| 45 |
1 |
250 MCM |
1 |
2-14 |
2-14 |
| 50 |
1 |
250 MCM |
1 |
2-14 |
2-14 |
| 75 |
1 |
350 MCM |
1 |
2 / 0-6 |
2 / 0-6 |
| 112.5 |
1 |
500 MCM |
1 |
2 / 0-6 |
2 / 0-6 |
| 150 |
2 |
350 MCM |
1 |
250 MCM |
2 / 0-6 |
| 225 |
2 |
500 MCM |
1 |
350 MCM |
350 MCM |
| 300 |
3 |
500 MCM |
1 |
500 MCM |
350 MCM
|
Technical Drawing
Isolation : 3 Phases
Isolation : 3 Phases
Full Load Current: Full Load Current (amps)
| KVA |
208 |
240 |
440 |
460 |
480 |
600 |
| 15 |
41.6 |
36.1 |
19.7 |
18.8 |
18 |
14.4 |
| 30 |
83.3 |
72.2 |
39.4 |
37.6 |
36.1 |
28.9 |
| 45 |
125 |
108 |
59.1 |
56.4 |
54.1 |
43.3 |
| 75 |
208 |
180 |
98.4 |
94.1 |
90.2 |
72.2 |
| 112.5 |
312 |
270 |
147 |
141 |
135 |
108 |
| 150 |
416 |
360 |
196 |
188 |
180 |
144 |
| 225 |
624 |
541 |
295 |
282 |
270 |
216 |
| 300 |
833 |
721 |
393 |
376 |
360 |
288 |
| 450 |
1246 |
1082 |
590 |
564 |
541 |
433 |
| 600 |
1665 |
1443 |
787 |
753 |
721 |
577 |
| 750 |
2082 |
1804 |
984 |
941 |
902 |
721 |
| 1000 |
2776 |
2405 |
1312 |
1255 |
1202 |
962 |
Connectors Type Connectors By Phase
| KVA |
Nb |
120- 208 VOLTS |
Nb |
480 VOLTS |
GROUND |
| 15 |
1 |
2-14 |
1 |
2-14 |
2-14 |
| 30 |
1 |
2 / 0-6 |
1 |
2-14 |
2-14 |
| 45 |
1 |
250 MCM |
1 |
2-14 |
2-14 |
| 75 |
1 |
350 MCM |
1 |
2 / 0-6 |
2 / 0-6 |
| 112.5 |
1 |
500 MCM |
1 |
2 / 0-6 |
2 / 0-6 |
| 150 |
1 |
350 MCM |
1 |
250 MCM |
2 / 0-6 |
| 225 |
1 |
500 MCM |
1 |
350 MCM |
350 MCM |
| 300 |
1 |
500 MCM |
1 |
500 MCM |
350 MCM |
| 450 |
1 |
BUS BAR |
1 |
BUS BAR |
350 MCM |
| 600 |
1 |
BUS BAR |
1 |
BUS BAR |
BUS BAR |
| 750 |
1 |
BUS BAR |
1 |
BUS BAR |
BUS BAR |
| 1000 |
1 |
BUS BAR |
1 |
BUS BAR |
BUS BAR |
Technical Drawing
Isolation : 3 Phases
|
|